The complete solution for monitoring of temperature, humidity and other values. For mounting to 19″ rack – one rack unit 1U. Enables to build in the optional MP016 output relays module with 16 relays – see Optional accessories.
Applications:
Main advantage – user configurable inputs from PC program without any need to open the data logger unit. Each data logger contains 16 inputs for measurement and record of both analog and two-state values. Each input is individually configurable from user PC program to one from 17 measuring ranges.
Also signals from sensors working on RS485 bus with ModBus or Advantech protocol can be recorded.
Universal sixteen channel data logger is designed for data acquisition from sensors of variety values, alarm state indication, optionally for control of consecutive processes.
Data is possible to download to the PC via USB, RS232, Ethernet interfaces or GSM modem for processing.
Free program for monitoring system for Windows is ready to download.
Each data logger input can be configured by the user from PC program depending on input signal character for measurement of dc current and voltage of different ranges, signals from RTD temperature sensors and thermocouples or dual-state signals with parameters in accordance with the table.
Inputs are not galvanically isolated from each other.
PARAMETERS OF CONFIGURABLE INPUTS | ||||
---|---|---|---|---|
Measured value | Accuracy | Note | ||
dc current 4 to 20 mA |
±0.1% FS (±0.02mA) | either from active source connected between COM and GND terminals or passive sensor connected between terminals +24V and COM | ||
dc voltage -10V to +10V |
±0.1% FS (±10 mV) |
input resistance approximately 10 Mohms, input terminals IN and COM |
||
dc voltage -1V to +1V |
±0.1% FS (±1 mV) |
input resistance approximately 10 Mohms, input terminals IN and COM |
||
dc voltage -100mV to +100mV |
±0.1% FS (±100 uV) |
input resistance approximately 10 Mohms, input terminals IN and COM |
||
dc voltage -18mV to +18mV |
±0.1% FS (±18 uV) |
input resistance approximately 10 Mohms, input terminals IN and COM |
||
thermocouple K (NiCr-Ni) -200 to +1300°C |
±0.3% from reading + 1.5°C | linearized, cold junction compensation, input terminals IN and COM |
||
thermocouple N (NiCrSi-NiSiMg) -200 to +1300°C |
±0.3% from reading + 1.5°C | linearized, cold junction compensation, input terminals IN and COM |
||
thermocouple J (Fe-Co) -200 to +750°C |
±0.3% from reading + 1.5°C | linearized, cold junction compensation, input terminals IN and COM |
||
thermocouple S (Pt10%Rh-Pt) 0 to +1700°C |
±0.3% from reading + 1.5°C | linearized, cold junction compensation, input terminals IN and COM |
||
thermocouple B (Pt30%Rh-Pt) +100 to +1800°C |
±0.3% from reading + 1.0°C from +300 to +1800°C |
linearized, without cold junction compensation, input terminals IN and COM |
||
thermocouple T (Cu-CuNi) -200 to +400°C |
±0.3% from reading + 1.5°C | linearized, cold junction compensation, input terminals IN and COM |
||
Platinum temperature sensor Pt100 -200 to +600°C |
±0.2°C from -200 to +100°C ±0.2% from reading from +100 to +600°C |
two-wire connection, measuring current approximately 0.8mA in pulse 50ms, input terminals IN and COM |
||
Platinum temperature sensor Pt1000 -200 to +600°C |
±0.2°C from -200 to +100°C ±0.2% from reading from +100 to +600°C |
two-wire connection, measuring current approximately 0.5mA in pulse 50ms, input terminals IN and COM |
||
Nickel temperature sensor Ni1000/6180ppm -50 to +250°C |
±0.2°C from -50 to +100°C ±0.2% from reading from +100 to +250°C |
two-wire connection, measuring current approximately 0.5mA in pulse 50ms, input terminals IN and COM |
||
two-wire measurement of resistance 0 to 300 Ohms |
0.1% FS (±0.3 Ohms) |
measuring current approximately 0.8mA / 50ms, input terminals IN and COM |
||
two-wire measurement of resistance 0 to 3000 Ohms |
0.1% FS (±3 Ohms) |
measuring current approximately 0.5mA / 50ms, input terminals IN and COM |
||
two-wire measurement of resistance 0 to 10000 Ohms |
0.1% FS (±10 Ohms) |
measuring current approximately 0.1mA / 50ms, input terminals IN and COM |
Binary input for two-state signal | input voltage for state “L” (IN-COM) < 0.8 V (Rin < 1 kOhm). resistance of closed contact for state “L” (IN-COM) < 1 kOhm. input voltage for state “H” (IN-COM) > 2 V. resistance of closed contact for state “H” (IN-COM) > 10 kOhm. minimum duration for sensing of change: 200ms. |
RS485IN – input for serial signal RS485 – optionally |
E.g. data acquisition from temperature, humidity, pressure sensors Tx41x, Hx43x. input serves for reading from devices supporting protocol ModBus RTU or Advantech. Connected to terminals next to terminals for channel 15 and 16. Input can work with 16 devices. Maximum speed 115200Bd. Galvanically isolated. |
Figure: rear view of data logger inputs with switch for selection of power voltage 12Vdc/24Vdc for connected sensors. Serial input RS485IN is optional.
Figure: front view – communication interface, alarm outputs, connection of power. Ethernet interface is optional.
Features of Ethernet interface:
Ethernet interface Data logger is designed for connection to standard computer network. The 10 and 100Mb/s Ethernet is supported.No need to build new data lines. Thanks this installation cost are essentially reduced and instant easy start of monitoring system operation is enabled. |
Modbus protocol Enables to read actually measured values by means of industrial standard Modbus. Data is available in several formats. Protocol is suitable for implementing of MS data logger to SCADA system. |
SNMPv1 protocol Actually measured values can be acquired by means of SNMPv1 protocol. MIB tables are available for free.Designed especially for IT applications and use in “managed” computer networks. |
Fast data download Record download speed was increased four-times from previous MS5 data logger generation. |
SOAP protocol Protocol designed for data logger integration to own www infrastructure. Available actual values can be captured by www server (Apache, IIS) and processed by the user.Communication protocol SOAP version 1.1. is supported. By means of this protocol data logger sends actual values in preset intervals to specified server. |
Syslog protocol Syslog message is sent after alarm state or data logger error appears. Syslog is compatible with RFC5424. |
Data logger sends warning emails up to three different addresses. E-mail is immediately sent after alarm state of monitored technological process appears. User is also informed on error states of device itself (measuring channel error, fulfilling of internal memory, self-test error). |
XML file Actual values can be downloaded to XML file. This option is suitable for data logger integration to SCADA systems. |
Data logger display Network parameters can be set directly from data logger display. It is possible to change IP address, subnetwork mask and initial gate. |
Secured WEB server WWW server is built in the device. Here it is possible to monitor actual values, alarm states and information on data logger.Also access password for www pages can be entered. WWW pages are user modifiable. Free SDK description is available to create own www pages. |
SNMP Trap SNMP Traps are sent after alarm state or device error appears. |
Database system Prepared for connection to database system including online values transfer. |
WWW remote conditions Control of remote condition and relays is enabled also via www interface. |
Technical data:
Technical parameters | Value |
---|---|
Total memory capacity | 2MB (up to 480 000 values) |
Memory type | internal SRAM, backed-up by Lithium battery |
Data logging modes | noncyclic – logging stops after filling the memory cyclic – after filling memory oldest data is overwritten by new |
Data logging interval | adjustable individually for all input channels from 1 second to 24 hours |
Real time clock | year, leap year, month, day, hour, minute, second, backed-up by Lithium battery |
Resolution of the AD converter (analog channels) | 16 bits, conversion duration approximately 60ms/channel |
Communication speed | 9600, 19200, 57600, 115200 Bd, 230400* Bd (* applicable for USB, Ethernet) |
Power | 24Vdc, consumption of data logger itself approximately 80 mA |
Operating temperature range | 0 to +50°C |
Dimensions | 483 x 190 x 44 mm (W x D x H) – one rack unit 1U |
Protection | IP20 |
Weight | approximately 800 g |
Warranty | 2 years |
Accesorii optionale:
1. Alimentatoare si adaptoare:
2. Elemente de fixare:
3. Comunicatii retea/GSM/Wi-Fi si convertoare:
4. Afisaje externe si accesorii:
5. Module releu si accesorii:
6. Alte accesorii:
7. Protectie suplimentara:
8. Senzori de temperatura:
© 2019 Sincro. All Rights Reserved. Developed by ALY Media
Sincro utilizează fişiere de tip cookie pentru a personaliza și îmbunătăți experiența ta pe Website-ul nostru. Te informăm că ne-am actualizat politicile pentru a integra în acestea si în activitatea curentă a Sincro cele mai recente modificări propuse de Regulamentul (UE) 2016/679 privind protecția persoanelor fizice în ceea ce privește prelucrarea datelor cu caracter personal și privind libera circulație a acestor date. Înainte de a continua navigarea pe Website-ul nostru te rugăm să aloci timpul necesar pentru a citi și înțelege conținutul Politicii de Cookie. Prin continuarea navigării pe Website-ul nostru confirmi acceptarea utilizării fişierelor de tip cookie conform Politicii de Cookie. Nu uita totuși că poți modifica în orice moment setările acestor fişiere cookie urmând instrucțiunile din Politica de Cookie.